Temperature Ranges
Heat: 45 – 79°F (7 – 26°C)
Cool: 58 – 92°F (14 – 33°C)
Display: 40 – 100°F (5 – 37°C)
Sensitivity: +/- 1°F (0.5°C)
Equipment Interface Operating: -40o to 160oF (-40o to 70oC)
Thermostat Operating: 32o to 130oF (0o to 55oC)
Humidity Range
Humidify: 20 to 50% R.H
Dehumidify: 30 to 60% R.H
Display: 0 - 90% R.H
Sensitivity: +/- 2% R.H.
Operating: 5 – 95% R.H non-condensing
Dimensions
Thermostat: 5.5”W x 3.25”H x 1”D (139.5mm H x 82.5mm W x 25mm D)
Equipment Interface: 4.6”W x 10”H x 1.3”D (118mm W x 254mm H x 32mm D)
Power
AC Transformer - 24 VAC - 3VA Minimum (not included)
Battery – CR2032 – 3V lithium coin cell (included),
Power Adaptor - #EB-PS-01 - 120V 50/60Hz to 12V DC 1A (not included)
Wiring Specifications
Refer to this table to determine maximum wire lengths allowed:
Thermostat to Equipment Interface:
18 AWG 20 AWG 22 AWG
1250ft/380m 790ft/240m 500ft/150m
Equipment Interface to Heating/Air Equipment:
18 AWG 20 AWG 22 AWG
128ft/39m 80ft/24m 50ft/15m